Hour Fire Rated VerticalWall Cladding System (Rockwool) - 0.35 ‘U’Value
This system has been designed for use as a non-load bearing external fire wall situated at least 1 metre away from a relevant boundary. Secured outside rail the construction incorporates Rockwool insulation and satisfies the criteria for 4 hours integrity (15 or 30 mins insulation) when assessed to comply with BS476 Part 22: 1987 in relation to internal fire exposure and installed in accordance with Approved Document B (Fire Spread) Building Regulations 2000.

Structural Frame
To be protected using suitable
materials providing a fire
resistance period equal to the
cladding system. Support
cladding from suitable
structural element, e.g: Fire
rated eaves beam.
Cladding Rails
Supplied in shorter lengths
than normal with slotted holes
to facilitate expansion. Install in
single span condition using
16mm diameter steel bolts with
steel and plastic washers. Rail
centres for cladding span not to
exceed 2m
.
Internal Lining
To meet 30 minute insulation
period, stitch lining panel side
laps at 300mm centres using
steel rivets.
e.g:TSPD 44 BS or equivalent.
Vapour Control
Layer Lining Panel - Seal side and
end laps.
Insulation
Compress between lining panel
and reverse face of spacer bar.
External Cladding
Where deemed necessary stitch
side laps using 6.3mm diameter
steel self drilling screws.
![]()
WFRC No - 141175AR
Internal Fire Assessment
BS476 Part 22:1987 Compliant
Stability: 240 minutes
Integrity: 240 minutes
Insulation; 15 minutes or 30 minute options
Click here to download - VRF35 Data Sheet
![]()